48361

48361

在产

Temperature Converter with Trip Values

查看国产替代问 AI FAE

全部替代型号

查看完整报告

技术参数

电源
Current outputmax. 20 µA
Current range0 ... 20 mA or 4 ... 20 mA
Current range 0 ... 20 mA or 4 ... 20 mA Open loop voltage max. 24 V DC Load max. 650 Ω Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43)Current range | 0 ... 20 mA or 4 ... 20 mA | Open loop voltage | max. 24 V DC | Load | max. 650 Ω | Fault signal | downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43)
Interface/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Measuring currentapprox. 400 µA
Open loop voltagemax. 5 V with resistance measuring sensor
Output III/power supply and collective errorreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Power dissipation/power consumption≤ 2 W / 2.2 W
Rated currentI r | approx. 100 mA
Rated voltageU r | 20 ... 30 V DC
Voltage0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV
交流 / 直流特性
Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A Mechanical life 5 x 10 7 switching cycles Energized/De-energized delay approx. 20 ms / approx. 20 msContact loading | 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A | Mechanical life | 5 x 10 7 switching cycles | Energized/De-energized delay | approx. 20 ms / approx. 20 ms
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Output I, II against eachotherreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
环境与封装
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Height119 mm
Height 119 mm Width 40 mm Depth 115 mmHeight | 119 mm | Width | 40 mm | Depth | 115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Temperature effectInput: 0.005 %/K (50 ppm) of span ; current output: 0.005 %/K (50 ppm) of span
其他
Cold junction compensationexternal and internal
Cold junction compensation external and internal Measurement loop monitoring sensor breakageCold junction compensation | external and internal | Measurement loop monitoring | sensor breakage
Collective error messagePower Rail
Configurationvia operating buttons via PACTware
Connectionterminals 23+, 24- or power feed module/Power Rail
Connection sidefield side
Contact loading250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A
Control elementsControl panel
Degree of protectionIEC 60529:2001
Depth115 mm
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)Directive 2014/30/EU | EN 61326-1:2013 (industrial locations)
Directive 2014/35/EUEN 61010-1:2010
Directive 2014/35/EU EN 61010-1:2010Directive 2014/35/EU | EN 61010-1:2010
Display elementsLEDs , display
Electromagnetic compatibilityNE 21:2007
Fault signaldownscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43)
Input/Other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Input resistance≥ 250 kΩ (0 ... 10 V) min. 1 MΩ (0 ... 1 V, -100 ... 100 mV)
Labelingspace for labeling at the front
Lead resistancemax. 50 Ω
Loadmax. 650 Ω
Mass300 g
Measurement loop monitoringsensor breakage, sensor short-circuit
Mechanical life5 x 10 7 switching cycles
Output I, IIrelay
Output IIIAnalog current output
Output I, II/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Potentiometer0.8 ... 20 kΩ
Programming interfaceprogramming socket
RTDPt100, Pt500, Pt1000, Ni100, Ni1000
Safety Integrity Level (SIL)SIL 2
Sampling rateapprox. 700 ms
Signal typeAnalog input
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Thermocouplestype B, E, J, K, L, N, R, S, T (IEC 584-1: 1995)
Types of measuring2-, 3-, 4-wire technology
Types of measuring 2-, 3-, 5-wire technologyTypes of measuring | 2-, 3-, 5-wire technology
Width40 mm

器件图片

技术资料

该型号暂未收录资料。