All alternatives
View full reportTechnical parameters
| Power | |
|---|---|
| Current output | max. 20 µA |
| Current range | 0 ... 20 mA or 4 ... 20 mA |
| Current range 0 ... 20 mA or 4 ... 20 mA Open loop voltage max. 24 V DC Load max. 650 Ω Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43) | Current range | 0 ... 20 mA or 4 ... 20 mA | Open loop voltage | max. 24 V DC | Load | max. 650 Ω | Fault signal | downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43) |
| Interface/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Measuring current | approx. 400 µA |
| Open loop voltage | max. 5 V with resistance measuring sensor |
| Output III/power supply and collective error | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Power dissipation/power consumption | ≤ 2 W / 2.2 W |
| Rated current | I r | approx. 100 mA |
| Rated voltage | U r | 20 ... 30 V DC |
| Voltage | 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV |
| AC and DC characteristics | |
| Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A Mechanical life 5 x 10 7 switching cycles Energized/De-energized delay approx. 20 ms / approx. 20 ms | Contact loading | 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A | Mechanical life | 5 x 10 7 switching cycles | Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
| Output I, II against eachother | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Environment and package | |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 |
| Height | 119 mm |
| Height 119 mm Width 40 mm Depth 115 mm | Height | 119 mm | Width | 40 mm | Depth | 115 mm |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Temperature effect | Input: 0.005 %/K (50 ppm) of span ; current output: 0.005 %/K (50 ppm) of span |
| Other | |
| Cold junction compensation | external and internal |
| Cold junction compensation external and internal Measurement loop monitoring sensor breakage | Cold junction compensation | external and internal | Measurement loop monitoring | sensor breakage |
| Collective error message | Power Rail |
| Configuration | via operating buttons via PACTware |
| Connection | terminals 23+, 24- or power feed module/Power Rail |
| Connection side | field side |
| Contact loading | 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A |
| Control elements | Control panel |
| Degree of protection | IEC 60529:2001 |
| Depth | 115 mm |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Directive 2014/30/EU EN 61326-1:2013 (industrial locations) | Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Directive 2014/35/EU | EN 61010-1:2010 |
| Directive 2014/35/EU EN 61010-1:2010 | Directive 2014/35/EU | EN 61010-1:2010 |
| Display elements | LEDs , display |
| Electromagnetic compatibility | NE 21:2007 |
| Fault signal | downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43) |
| Input/Other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Input resistance | ≥ 250 kΩ (0 ... 10 V) min. 1 MΩ (0 ... 1 V, -100 ... 100 mV) |
| Labeling | space for labeling at the front |
| Lead resistance | max. 50 Ω |
| Load | max. 650 Ω |
| Mass | 300 g |
| Measurement loop monitoring | sensor breakage, sensor short-circuit |
| Mechanical life | 5 x 10 7 switching cycles |
| Output I, II | relay |
| Output III | Analog current output |
| Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Potentiometer | 0.8 ... 20 kΩ |
| Programming interface | programming socket |
| RTD | Pt100, Pt500, Pt1000, Ni100, Ni1000 |
| Safety Integrity Level (SIL) | SIL 2 |
| Sampling rate | approx. 700 ms |
| Signal type | Analog input |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Thermocouples | type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995) |
| Types of measuring | 2-, 3-, 4-wire technology |
| Types of measuring 2-, 3-, 5-wire technology | Types of measuring | 2-, 3-, 5-wire technology |
| Width | 40 mm |
Documents
No documents are linked to this part yet.