技术参数

电源
Auxiliary voltage (output)U AUX | 20 ... 30 V DC PELV
Current2 A per output TB ≤ 40 °C: 6 A total TB ≤ 60 °C: OUT1+OUT2 max. 3 A, OUT3 max. 2 A
Current loading capacity500 mA , overload and short-circuit protected
Input current≤ 8 mA (limited internally)
Rated operating currentI e | ≤ 35 mA
Rated operating voltageU e | 26.5 ... 31.6 V from AS-Interface
Supplyfrom external auxiliary voltage U AUX
Voltage≥ (U AUX - 0.5 V)
交流 / 直流特性
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Signal delay< 1 ms (input/AS-Interface)
环境与封装
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Mounting2 clips with ∅ 8 mm drill hole
Storage temperature-30 ... 85 °C (-22 ... 185 °F)
其他
AS-InterfaceEN 62026-2:2013
AS-Interface specificationV3.0
Cable length0.7 m (Inputs) , 1.5 m (X1, X2)
ConnectionAS-Interface, AUX: Insulation piercing technology Yellow flat cable/black flat cable Inputs/outputs: M12 round plug connector in accordance with EN 61076-2-101 Inputs: LF type (4-pin, bushing contacts, screw lock, A-coded) Matching connector: LM type or similar Outputs: LF type (4-pin, bushing contacts, screw lock, A-coded) Matching connector: LM type or similar
Degree of protectionEN 60529:2000
Directive 2014/30/EUEN 62026-2:2013
Directive 2014/30/EU EN 62026-2:2013Directive 2014/30/EU | EN 62026-2:2013
Emitted interferenceEN 61000-6-4:2007
Fieldbus standardEN 62026-2:2013
ID1 code7
ID2 codeE
ID codeA
InputEN 61131-2:2007
IO code7
IO code 7 ID code A ID1 code 7 ID2 code EIO code | 7 | ID code | A | ID1 code | 7 | ID2 code | E
LED AUXext. auxiliary voltage U AUX ; dual LED green/red green: voltage OK red: reverse voltage
LED FAULTerror display; LED red red: communication error or address is 0 red flashing: overload of sensor power supply or overload of outputs or external auxiliary voltage U AUX missing
LED INswitching state (input); 4 LED yellow
LED OUTSwitching state (output); 3 LED yellow
LED PWRAS-Interface voltage; green LED green: voltage OK flashing green: address 0 or overload of sensor power supply or overload of outputs or external auxiliary voltage U AUX missing
Mass260 g
MTBF110 a
Node typeA/B node
NoteThe flat cable routing is designed for 100 actuation cycles
Number/Type4 Inputs for 3-wire sensors (PNP), DC
ProfileS-7.A.E
Required gateway specification≥ V2.1
Switching pointaccording to DIN EN 61131-2 0 (undamped) ≤ 0.5 mA 1 (damped) ≥ 2.0 mA
UL File NumberE223772 "For use in NFPA 79 Applications only"