103844

103844

在产

Inductive sensor

问 AI FAE

全部替代型号

查看完整报告

技术参数

电源
Nominal voltageU o | 8.2 V (R i approx. 1 kΩ)
交流 / 直流特性
Switching frequencyf | 0 ... 200 Hz
环境与封装
Ambient temperature-40 ... 100 °C (-40 ... 212 °F)
其他
Assured operating distances a | 0 ... 6.48 mm
Bending radius> 10 x cable diameter
Cable diameter6 mm ± 0.2 mm
Cable diameter 6 mm ± 0.2 mm Bending radius > 10 x cable diameter Material silicone Core cross section 0.75 mm 2 Length L 10 mCable diameter | 6 mm ± 0.2 mm | Bending radius | > 10 x cable diameter | Material | silicone | Core cross section | 0.75 mm 2 | Length | L | 10 m
Connection typecable
Control drawing116-0454
Core cross section0.75 mm 2
Degree of protectionIP68
Diagnostic Coverage (DC)0 %
Diameter18 mm
Equipment protection level DaIECEx PTB 11.0092X
Equipment protection level Dc (tc)IECEx TUR 21.0018X
Equipment protection level GaIECEx PTB 11.0092X
Equipment protection level GbIECEx PTB 11.0092X
Equipment protection level Gc (ec)IECEx TUR 21.0017X
Equipment protection level MbIECEx PTB 11.0092X
Hazardous LocationE501628
Hazardous Location 2020322315002308 2024322315005947 2024322315005860Hazardous Location | 2020322315002308 2024322315005947 2024322315005860
Housing materialCrastin (PBT), black
Installationnon-flush
LengthL | 10 m
Length 39 mm Diameter 18 mmLength | 39 mm | Diameter | 18 mm
Materialsilicone
Measuring plate detected≤ 1 mA
Measuring plate not detected≥ 3 mA
Measuring plate not detected ≥ 3 mA Measuring plate detected ≤ 1 mAMeasuring plate not detected | ≥ 3 mA | Measuring plate detected | ≤ 1 mA
Mission Time (T M )20 a
MTTF d11850 a
NAMUREN 60947-5-6:2000 IEC 60947-5-6:1999
NAMUR EN 60947-5-6:2000 IEC 60947-5-6:1999 Standards EN IEC 60947-5-2NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | Standards | EN IEC 60947-5-2
Ordinary LocationE87056
Ordinary Location E87056 Hazardous Location E501628 Control drawing 116-0454Ordinary Location | E87056 | Hazardous Location | E501628 | Control drawing | 116-0454
Output typeNAMUR with safety function
Rated operating distances n | 8 mm
Reduction factor r 3040.85
Reduction factor r Al0.4
Reduction factor r Cu0.3
Safety Integrity Level (SIL)up to SIL3 acc. to IEC 61508 Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1. Consider the "exida Functional Safety Assessment" document which is available on www.pepperl-fuchs.com as an integral part of this product's documentation.
Scope of deliverySupplied with 2 nuts
Sensing faceCrastin (PBT), black
StandardsEN IEC 60947-5-2
Switching functionNormally closed (NC)
UL approvalcULus Listed Load Type: Resistive Circuitry: Class 2 Power Source Enclosure Type Rating: Type 1 Supply/Switching Voltage: 8.2 V DC
Use in the hazardous areasee instruction manuals

器件图片

技术资料

该型号暂未收录资料。