全部替代型号
查看完整报告技术参数
| 电源 | |
|---|---|
| Current loading capacity | ≤ 200 mA, overload and short-circuit protected |
| Input current | ≤ 8 mA (limited internally) |
| Rated operating current | I e | ≤ 80 mA (without sensors) / max. 280 mA |
| Rated operating voltage | U e | 26.5 ... 31.6 V from AS-Interface |
| Supply | from AS-Interface |
| Voltage | 21 ... 31 V |
| 交流 / 直流特性 | |
| Noise immunity | EN 61000-6-2:2005 EN 62026-2:2013 |
| Signal delay | < 1 ms (input/AS-Interface) |
| 环境与封装 | |
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Height | 35 mm |
| Height 35 mm Width 57.4 mm Length 151.6 mm | Height | 35 mm | Width | 57.4 mm | Length | 151.6 mm |
| Mounting | Mounting plate |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| 其他 | |
| 0 (unattenuated) | ≤ 2 mA |
| 0 (unattenuated) ≤ 2 mA 1 (attenuated) ≥ 6 mA | 0 (unattenuated) | ≤ 2 mA | 1 (attenuated) | ≥ 6 mA |
| 1 (attenuated) | ≥ 6 mA |
| Altitude | ≤ 2000 m above MSL |
| AS-Interface | EN 62026-2:2013 |
| AS-Interface specification | V3.0 |
| Connection | cable piercing method flat cable yellow inputs: M12 round connector |
| Degree of protection | EN 60529:2000 |
| Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
| Directive 2014/30/EU EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 | Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
| Emitted interference | EN 61000-6-4:2007 |
| Fieldbus standard | EN 62026-2:2013 |
| Housing | PBT |
| Housing PBT | Housing | PBT |
| ID1 code | Node 1: 1 Node 2: 2 |
| ID2 code | 2 |
| ID code | A |
| Input | EN 61131-2 |
| IO code | 0 |
| IO code 0 ID code A ID1 code Node 1: 1 Node 2: 2 ID2 code 2 | IO code | 0 | ID code | A | ID1 code | Node 1: 1 Node 2: 2 | ID2 code | 2 |
| LED IN | switching state (input); 8 LED yellow |
| LED PWR/FAULT | 2 Dual LEDs green/red green: AS-Interface voltage red: Communication error yellow/red flashing: Address 0 green/red flashing: Sensor supply overload |
| Length | 151.6 mm |
| Mass | 230 g |
| Node type | Double A/B node |
| Number/Type | 2x 4 inputs for 2- or 3-wire sensors (PNP), DC alternative 2x 2 inputs for 4-wire sensors (PNP), DC |
| Pollution degree | 3 |
| Profile | S-0.A.2 |
| Protection class | III |
| Relative humidity | 85 % , non-condensing |
| Required gateway specification | ≥ V2.1 |
| Shock and impact resistance | 30 g , 11 ms in 6 spatial directions 3 shocks 10 g , 16 ms in 6 spatial directions 1000 shocks |
| Surge protection | U e : Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral |
| Switching point | according to DIN EN 61131-2 (Type 2) |
| Tightening torque, cable gland | 0.4 Nm |
| UL File Number | E223772 |
| Vibration resistance | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
| Width | 57.4 mm |
器件图片