All alternatives

View full report

Technical parameters

Power
Nominal voltageU o | 8.2 V (R i approx. 1 kΩ)
AC and DC characteristics
Switching frequencyf | 0 ... 100 Hz
Environment and package
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Other
ANZEx18.3018X
Assured operating distances a | 0 ... 16.2 mm
CML approvalon request
Connection typeterminal compartment
Core cross sectionup to 2.5 mm 2
Degree of protectionIP67
Diagnostic Coverage (DC)0 %
Diameter40 mm
Equipment protection level DaIECEx PTB 11.0037X
Equipment protection level GbIECEx PTB 11.0037X
Equipment protection level Gb IECEx PTB 11.0037X Equipment protection level Da IECEx PTB 11.0037X Equipment protection level Mb IECEx PTB 11.0037XEquipment protection level Gb | IECEx PTB 11.0037X | Equipment protection level Da | IECEx PTB 11.0037X | Equipment protection level Mb | IECEx PTB 11.0037X
Equipment protection level Gb PTB 00 ATEX 2048 X Equipment protection level Da PTB 00 ATEX 2048 XEquipment protection level Gb | PTB 00 ATEX 2048 X | Equipment protection level Da | PTB 00 ATEX 2048 X
Equipment protection level MbIECEx PTB 11.0037X
Hazardous Location2020322315002258
Hazardous Location 2020322315002258Hazardous Location | 2020322315002258
Housing materialPBT
Installationnon-flush
Length95 mm
Length 95 mm Diameter 40 mmLength | 95 mm | Diameter | 40 mm
Measuring plate detected≤ 1 mA
Measuring plate not detectedmin. 3 mA
Measuring plate not detected min. 3 mA Measuring plate detected ≤ 1 mAMeasuring plate not detected | min. 3 mA | Measuring plate detected | ≤ 1 mA
Mission Time (T M )20 a
MTTF d11400 a
NAMUREN 60947-5-6:2000 IEC 60947-5-6:1999
NAMUR EN 60947-5-6:2000 IEC 60947-5-6:1999 Standards EN IEC 60947-5-2NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | Standards | EN IEC 60947-5-2
Output typeNAMUR
Rated operating distances n | 20 mm
Reduction factor r 3040.85
Reduction factor r Al0.4
Reduction factor r Cu0.3
Sensing facePBT
StandardsEN IEC 60947-5-2
Switching functionNormally closed (NC)
UL approvalcULus Listed Load Type: Resistive Circuitry: Class 2 Power Source Enclosure Type Rating: Type 1 Supply/Switching Voltage: 8.2 V DC
Use in the hazardous areasee instruction manuals

Documents

No documents are linked to this part yet.