All alternatives
View full reportTechnical parameters
| Power | |
|---|---|
| Minimum switch current | 10 mA / 24 V DC |
| Power consumption | < 1.3 W |
| Power dissipation | < 1.3 W |
| Rated current | I r | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card) |
| Rated voltage | U r | 19 ... 30 V DC loop powered |
| AC and DC characteristics | |
| Energized/De-energized delay | 150 ms / 150 ms |
| Switching frequency | < 3 Hz |
| Environment and package | |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating. |
| Dimensions | 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Other | |
| Connection | loop powered |
| Connection side | control side |
| Contact loading | 125 V AC/3 A/cos φ 0.7; 30 V DC/3 A resistive load 125 V AC / 1/8 HP |
| Degree of protection | IEC 60529:2013 |
| Directive 2006/42/EC | EN IEC 62061:2021 , EN/ISO 13849-1:2015 |
| Directive 2006/42/EC EN IEC 62061:2021 , EN/ISO 13849-1:2015 | Directive 2006/42/EC | EN IEC 62061:2021 , EN/ISO 13849-1:2015 |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Directive 2014/30/EU EN 61326-1:2013 (industrial locations) | Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Directive 2014/35/EU | EN 61010-1:2010+A1:2019+A1:2019/AC:2019 |
| Directive 2014/35/EU EN 61010-1:2010+A1:2019+A1:2019/AC:2019 | Directive 2014/35/EU | EN 61010-1:2010+A1:2019+A1:2019/AC:2019 |
| Display elements | LEDs |
| Electromagnetic compatibility | NE 21:2017 , EN 61326-3-1:2017 , EN IEC 61326-3-2:2018 |
| Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Labeling | space for labeling at the front |
| Mass | approx. 100 g |
| Mechanical life | 5 x 10 6 switching cycles |
| Performance level (PL) | PL e |
| Pulse/Pause ratio | 150 ms / 150 ms |
| Safety Integrity Level (SIL) | SIL 3 |
| Signal level | 0-signal: -5 ... 5 V 1-signal: 19 ... 26.5 V |
| Signal type | Digital Output |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Systematic capability (SC) | SC 3 |
| Test input | see functional safety manual |
| Test pulse length | max. 4 ms from DO card |
Documents
No documents are linked to this part yet.