All alternatives

View full report

Technical parameters

Power
Minimum switch current10 mA / 24 V DC
Power consumption< 1.5 W
Power dissipation< 1.5 W
Rated currentI r | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card)
Rated voltageU r | 19 ... 30 V DC loop powered
AC and DC characteristics
Energized/De-energized delay150 ms / 150 ms
Switching frequency< 3 Hz
Environment and package
Ambient temperature-20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating.
Dimensions12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Other
Connectionloop powered
Connection sidecontrol side
Contact loading253 V AC/3 A/cos φ 0.7; 30 V DC/3 A resistive load 253 V AC / 1/8 HP
Degree of protectionIEC 60529:2013
Directive 2006/42/ECEN IEC 62061:2021 , EN/ISO 13849-1:2015
Directive 2006/42/EC EN IEC 62061:2021 , EN/ISO 13849-1:2015Directive 2006/42/EC | EN IEC 62061:2021 , EN/ISO 13849-1:2015
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)Directive 2014/30/EU | EN 61326-1:2013 (industrial locations)
Directive 2014/35/EUEN 61010-1:2010+A1:2019+A1:2019/AC:2019
Directive 2014/35/EU EN 61010-1:2010+A1:2019+A1:2019/AC:2019Directive 2014/35/EU | EN 61010-1:2010+A1:2019+A1:2019/AC:2019
Display elementsLEDs
Electromagnetic compatibilityNE 21:2017 , EN 61326-3-1:2017 , EN IEC 61326-3-2:2018
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Labelingspace for labeling at the front
Massapprox. 100 g
Mechanical life5 x 10 6 switching cycles
Pulse/Pause ratio150 ms / 150 ms
Safety Integrity Level (SIL)SIL 3
Signal level0-signal: -5 ... 5 V 1-signal: 19 ... 26.5 V
Signal typeDigital Output
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Systematic capability (SC)SC 3
Test inputsee functional safety manual
Test pulse lengthmax. 4 ms from DO card

Documents

No documents are linked to this part yet.