All alternatives

View full report

Technical parameters

Power
Available voltage≥ 16 V at 20 mA ; ≥ 20 V at 4 mA , terminals 1+, 3; 4+, 6
CurrentI o | 93 mA
External supply (loop)2 ... 30 V DC If the external voltage is > 19 V, a load ≥ ((V - 19) / 0.02) Ω is required. V represents the value of the external voltage. The internal 250 Ω resistor at terminals 9 and 12 can be used as a load.
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V
Maximum safe voltageU m | 250 V (Attention! The rated voltage can be lower.)
Maximum safe voltage U m 250 V (Attention! The rated voltage can be lower.)Maximum safe voltage | U m | 250 V (Attention! The rated voltage can be lower.)
Open circuit voltage/short-circuit currentterminals 1+, 3; 4+, 6: 23 V / 25 mA
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
PowerP o | 634 mW
Power consumption≤ 2.6 W at maximum load
Power dissipation≤ 1.4 W at maximum load
Rated voltageU r | 18 ... 30 V DC
VoltageU o | 26.2 V
Voltage U i 30 V Current I i 115 mA Power P i max 1 W Voltage U o 2 V Current I o 8.5 mA Power P o 4.3 mWVoltage | U i | 30 V | Current | I i | 115 mA | Power | P i | max 1 W | Voltage | U o | 2 V | Current | I o | 8.5 mA | Power | P o | 4.3 mW
Voltage U o 26.2 V Voltage U q 27.25 V Current I o 115 mA Power P o 784 mWVoltage | U o | 26.2 V | Voltage | U q | 27.25 V | Current | I o | 115 mA | Power | P o | 784 mW
Voltage U o 26.2 V Voltage U q 27.25 V Current I o 93 mA Power P o 634 mWVoltage | U o | 26.2 V | Voltage | U q | 27.25 V | Current | I o | 93 mA | Power | P o | 634 mW
AC and DC characteristics
Frequency rangefield side into the control side: band width with 1 V pp signal 0 ... 7.5 kHz (-3 dB) safe area to hazardous area: band width with 1 V SS signal 0.3 ... 7.5 kHz (-3 dB)
Protection against electrical shockUL 61010-1:2012
Ripplewithin the supply tolerance
Rise time/fall time1 ms
Settling time2 ms
Environment and package
Ambient temperature-20 ... 60 °C (-4 ... 140 °F) extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions
Dimensions20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) (W x H x D) , housing type B2
Influence of ambient temperature≤ 0.25 µA/K
Influence of ambient temperature ≤ 0.25 µA/KInfluence of ambient temperature | ≤ 0.25 µA/K
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Other
CertificateCML 17 ATEX 3030X
ConnectionPower Rail or terminals 14+, 15-
Connection sidefield side
Control drawing116-0439 (cULus)
Control drawing 116-0439 (cULus)Control drawing | 116-0439 (cULus)
Degree of protectionIEC 60529:2001
Deviationat 20 °C (68 °F), 4 ... 20 mA ≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)Directive 2014/30/EU | EN 61326-1:2013 (industrial locations)
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN IEC 60079-11:2024
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN IEC 60079-11:2024Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN IEC 60079-11:2024
Display elementsLED
Electromagnetic compatibilityNE 21:2012 EN 61326-3-2:2008
Equipmentterminals 1+, 3-; 4+, 6-
EU-type examination certificateCML 17 ATEX 2031X
IECEx certificateIECEx CML 17.0016X
IECEx certificate IECEx CML 17.0016X IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 GcIECEx certificate | IECEx CML 17.0016X | IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc
Input[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V
Input resistancemax. 265 Ω terminals 2-, 3; 5-, 6 , max. 330 Ω terminals 1+, 3; 4+, 6
Input signal4 ... 20 mA
Labelingspace for labeling at the front
Load0 ... 600 Ω
MarkingII (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I Input [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] IMarking | II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I | Input | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Marking II 3G Ex ec IIC T4 GcMarking | II 3G Ex ec IIC T4 Gc
Massapprox. 200 g
Output/Outputfunctional insulation, rated insulation voltage 50 V AC
Output signal4 ... 20 mA (overload > 25 mA)
Safety Integrity Level (SIL)SIL 2
Signal typeAnalog input
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Systematic capability (SC)SC 3
UL approvalE106378

Documents

No documents are linked to this part yet.