All alternatives

View full report

Technical parameters

Power
Auxiliary voltage (output)U AUX | 24 V DC ± 15 % PELV
Current2 A per output 6 A total (TB ≤ 40 °C) 4 A total (TB ≤ 70 °C)
Current loading capacity≤ 200 mA, overload and short-circuit protected
Input current≤ 8 mA (limited internally)
Rated operating currentI e | ≤ 40 mA (without sensors) / max. 240 mA
Rated operating voltageU e | 26.5 ... 31.6 V from AS-Interface
Supplyfrom AS-Interface
Voltage21 ... 31 V
AC and DC characteristics
Noise immunityEN 61000-6-2:2005 EN 62026-2:2013
Signal delay< 1 ms (input/AS-Interface)
Environment and package
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Height35 mm
Height 35 mm Width 57.4 mm Length 151.6 mmHeight | 35 mm | Width | 57.4 mm | Length | 151.6 mm
MountingMounting plate
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Other
0 (unattenuated)≤ 2 mA
0 (unattenuated) ≤ 2 mA 1 (attenuated) ≥ 6 mA0 (unattenuated) | ≤ 2 mA | 1 (attenuated) | ≥ 6 mA
1 (attenuated)≥ 6 mA
Altitude≤ 2000 m above MSL
AS-InterfaceEN 62026-2:2013
AS-Interface specificationV3.0
ConnectionCable piercing method flat cable yellow/flat cable black inputs/outputs: M12 round connector
Degree of protectionEN 60529:2000
Directive 2014/30/EUEN 62026-2:2013
Directive 2014/30/EU EN 62026-2:2013Directive 2014/30/EU | EN 62026-2:2013
Emitted interferenceEN 61000-6-4:2007
Fieldbus standardEN 62026-2:2013
HousingPBT
Housing PBTHousing | PBT
ID1 code7
ID2 code2
ID codeA
InputEN 61131-2
IO code7
IO code 7 ID code A ID1 code 7 ID2 code 2IO code | 7 | ID code | A | ID1 code | 7 | ID2 code | 2
LED AUXext. auxiliary voltage U AUX ; dual LED green/red green: voltage OK red: reverse voltage
LED FAULTerror display; LED red red: communication error or address is 0 red flashing: overload of sensor power supply or outputs
LED INswitching state (input); 4 LED yellow
LED OUTSwitching status (output); 3 yellow/red LEDs Yellow: output active Red: output overload
LED PWRAS-Interface voltage; green LED green: voltage OK flashing green: address 0
Length151.6 mm
Mass230 g
Node typeA/B node
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC
Pollution degree3
ProfileS-7.A.2
Protection classIII
Relative humidity85 % , non-condensing
Required gateway specification≥ V2.1
Shock and impact resistance30 g , 11 ms in 6 spatial directions 3 shocks 10 g , 16 ms in 6 spatial directions 1000 shocks
Surge protectionU AUX , U in : Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral
Switching pointaccording to DIN EN 61131-2 (Type 2)
Tightening torque, cable gland0.4 Nm
UL File NumberE223772
Vibration resistance0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Width57.4 mm

Documents

No documents are linked to this part yet.