All alternatives

View full report

Technical parameters

Power
Auxiliary voltage (output)U AUX | 20 ... 30 V DC PELV
Current loading capacity≤ 140 mA from AS-Interface; overload and short-circuit resistant ≤ 600 mA from external auxiliary voltage U AUX , overload and short-circuit protected
Measuring currentfor Pt100: approx. 1 mA
Rated operating currentI e | ≤ 60 mA (without sensors) / max. 200 mA
Rated operating voltageU e | 26.5 ... 31.6 V from AS-Interface
Supplyfrom AS-Interface (switch position INT, default settings) or auxiliary voltage U EXT (switch position EXT)
AC and DC characteristics
AccuracyVoltage/current: 0.1% of accumulated value Pt100: 0.1% of indicated temperature [°C] + 0.3 °C
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Resolution16 Bit / 1 µA (current input) or 16 bit / 1 mV (voltage input) or 16 Bit / 0.1°C (temperature input)
Environment and package
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Height35 mm
Height 35 mm Diameter 85 mmHeight | 35 mm | Diameter | 85 mm
Housing PBT PC Mounting screw Stainless steel 1.4305 / AISI 303Housing | PBT PC | Mounting screw | Stainless steel 1.4305 / AISI 303
MountingMounting plate
Mounting screwStainless steel 1.4305 / AISI 303
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Temperature influenceVoltage/current: 20 ppm/K Pt100: (10 ppm of indicated temperature [°C] + 0.003 °C)/K
Other
Altitude≤ 2000 m above MSL
AS-InterfaceEN 62026-2:2013
AS-Interface specificationV3.0
Climatic conditionsFor indoor use only
ConnectionAS-Interface/U AUX : cable piercing method, flat cable yellow/flat cable black Inputs: M12 round connector
Degree of protectionEN 60529:2000
Diameter85 mm
Directive 2014/30/EUEN 62026-2:2013
Directive 2014/30/EU EN 62026-2:2013Directive 2014/30/EU | EN 62026-2:2013
Emitted interferenceEN 61000-6-4:2007
Fieldbus standardEN 62026-2:2013
HousingPBT PC
ID1 codeF
ID2 codeD
ID code3
InputEN 61131-2:2007
Input resistancecurrent input: max. 70 Ω voltage input: 100 kΩ
IO code7
IO code 7 ID code 3 ID1 code F ID2 code DIO code | 7 | ID code | 3 | ID1 code | F | ID2 code | D
LED ANALOGstatus of input signal; LED yellow off: not active on: signal within measuring range flashing: signal outside of measuring range
LED AS-i/FAULTStatus display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: peripheral fault
LED AUXext. auxiliary voltage U AUX ; dual LED green/red green: voltage OK red: reverse voltage
LED INT/EXTstatus display input supply; LED green green: input supply from AS-Interface off: input supply from auxiliary voltage
Mass200 g
Node typeStandard node
Number/Type2 analog inputs Current: 0 ... 20 mA/4 ... 20 mA voltage: 0 ... 10 V Pt100: -200 ... 850 °C
Pollution degree3
ProfileS-7.3.D
Protection classIII
Relative humidity85 % , non-condensing
Required gateway specification≥ V2.1
Surge protectionU AUX , U in : Over voltage category III, safe isolated power supplies (PELV)
Tightening torque, cable gland0.4 Nm
Tightening torque, housing screws1.8 Nm
UL File NumberE223772

Documents

No documents are linked to this part yet.