All alternatives

View full report

Technical parameters

Power
Currentmax. 240 mA
Nominal voltageU o | 8.2 V (R i approx. 1 kΩ)
Voltagemax. 32 V DC
AC and DC characteristics
Switching frequencyf | 0 ... 3 kHz
Time delay before availabilityt v | ≤ 1.1 ms
Environment and package
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Height35.5 mm
Height 35.5 mm Width 65 mm Length 77.5 mmHeight | 35.5 mm | Width | 65 mm | Length | 77.5 mm
Storage temperature-40 ... 100 °C (-40 ... 212 °F)
Other
Actual operating distances r | 2.7 ... 3.3 mm typ.
Actuating elementStainless steel 1.4305 / AISI 303 8.5 mm x 8.5 mm x 0.5 mm
Assured operating distances a | 0 ... 2.4 mm
Connection (system side)Cage tension spring terminals Stripped length 7 mm M20 x 1.5 cable gland usable thread length 11.5 mm screw-in depth max. 11.5 mm
Connection (valve side)Cage tension spring terminals
Control drawing116-0456
Core cross section (system side)1.5/2.5 mm 2 flexible/rigid
Core cross section (valve side)1.5/2.5 mm 2 flexible/rigid
Degree of protectionIP66 / IP67
Diagnostic Coverage (DC)0 %
Electromagnetic compatibilityNE 21:2007
Equipment protection level GaIECEx TUN 17.0021X
Equipment protection level Ga IECEx TUN 17.0021X Equipment protection level Gb IECEx TUN 17.0021X Equipment protection level Mb IECEx TUN 17.0021XEquipment protection level Ga | IECEx TUN 17.0021X | Equipment protection level Gb | IECEx TUN 17.0021X | Equipment protection level Mb | IECEx TUN 17.0021X
Equipment protection level Ga TÜV 99 ATEX 1479 X Equipment protection level Gb TÜV 99 ATEX 1479 X Equipment protection level Gc (ic) PF13CERT2895 XEquipment protection level Ga | TÜV 99 ATEX 1479 X | Equipment protection level Gb | TÜV 99 ATEX 1479 X | Equipment protection level Gc (ic) | PF13CERT2895 X
Equipment protection level GbIECEx TUN 17.0021X
Equipment protection level Gc (ic)PF13CERT2895 X
Equipment protection level MbIECEx TUN 17.0021X
Hazardous LocationE501628
Hazardous Location 2020322315002262Hazardous Location | 2020322315002262
Housing materialPBT
HysteresisH | typ. 5 %
Installationflush mountable
Length77.5 mm
Measuring plate detected≤ 1 mA
Measuring plate not detected≥ 3 mA
Measuring plate not detected ≥ 3 mA Measuring plate detected ≤ 1 mAMeasuring plate not detected | ≥ 3 mA | Measuring plate detected | ≤ 1 mA
Mission Time (T M )20 a
MTTF d1470 a
NAMUREN 60947-5-6:2000 IEC 60947-5-6:1999
NAMUR EN 60947-5-6:2000 IEC 60947-5-6:1999 Electromagnetic compatibility NE 21:2007 Standards EN IEC 60947-5-2NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | Electromagnetic compatibility | NE 21:2007 | Standards | EN IEC 60947-5-2
NEPSI certificateGYJ19.1410X
NEPSI certificate GYJ19.1410XNEPSI certificate | GYJ19.1410X
NoteLED switch-off
Ordinary LocationE87056
Ordinary Location E87056 Hazardous Location E501628 Control drawing 116-0456Ordinary Location | E87056 | Hazardous Location | E501628 | Control drawing | 116-0456
Output typeNAMUR
Rated operating distances n | 3 mm
Reduction factor r 3041
Reduction factor r Al0.5
Reduction factor r Brass0.6
Reduction factor r Cu0.4
Reduction factor r St371.3
Reverse polarity protectionreverse polarity protected
Safety Integrity Level (SIL)SIL 2
Sensing facePBT
Short-circuit protectionyes
StandardsEN IEC 60947-5-2
Suitable for 2:1 technologyyes , Reverse polarity protection diode not required
Switching function2 x normally closed (NC)
Switching state indicatorLED, yellow
Tightening torque, cable glandM20 x 1.5 ; max. 7 Nm M12 x 1.5 ; max. 1.5 Nm
Tightening torque, fastening screws≤ 5 Nm
Tightening torque, housing screws1 Nm
UL approvalcULus Listed Load Type: Resistive Circuitry: Class 2 Power Source Enclosure Type Rating: Type 1 Supply/Switching Voltage: 8.2 V DC
Use in the hazardous areasee instruction manuals
Valve status indicatorLED, yellow
Width65 mm