Полный отчётТехнические параметры
| Питание | |
|---|---|
| Current | resistance thermometer (RTD): sensor current ≤ 0.6 mA thermocouple (TC): sensor current 30 mA |
| Current limit | ≤ 25 mA |
| Rated voltage | U r | 8 ... 35 V DC 8 ... 30 V DC for hazardous area |
| Self current consumption | max. 3.5 mA |
| Характеристики по постоянному и переменному току | |
| Residual ripple | U pp ≤ 5 V at U b ≥ 13 V, f max = 1 kHz |
| Switch-on delay | t on | 4 s , during power up I a = 3.8 mA |
| Условия эксплуатации и корпус | |
| Ambient temperature | -40 ... 85 °C (-40 ... 185 °F) , for hazardous area see certificate |
| Dimensions | ∅44 x 22,5 mm (1.7 x 0.9 inch) |
| Storage temperature | -40 ... 100 °C (-40 ... 212 °F) |
| Другое | |
| Climate class | EN 60654, class C |
| Cold junction compensation | internal (Pt100) or external (0 ... 80 °C (273 ... 353 K)), accuracy ± 1 K |
| Configuration | via PC operating software, configuration set TXU 10L interface: PC interface connection cable TTL-/-RS 232 with plug |
| Connection | terminals 1, 2 |
| Construction type | connection head acc. to DIN 43729 form B, field housing |
| Degree of protection | IP00/IP66 installed |
| Directive 2004/108/EC (EMC) | emitted interference and noise immunity to EN 61326-1:2006 and EN 61326-2-3:2006 |
| Directive 94/9/EC (ATEX) | EN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2007 |
| Electromagnetic compatibility | NE 21 |
| Electromagnetic compatibility NE 21 Degree of protection EN 60529 Climate class EN 60654, class C Vibration resistance EN 60068-2-6 | Electromagnetic compatibility | NE 21 | Degree of protection | EN 60529 | Climate class | EN 60654, class C | Vibration resistance | EN 60068-2-6 |
| Explosion-hazardous area | ZELM 07 ATEX 0352 X , for additional certificates see www.pepperl-fuchs.com |
| Input/Output | safe galvanic isolation acc. to EN 50020, 3.75 kV AC |
| Lead resistance | resistance thermometer (RTD): max. 11 Ω per line |
| Load | (V s - 8)/0.025 A |
| Mass | approx. 40 g |
| Material | housing: PC potting: PUR |
| Maximum measured error | resistance thermometer (RTD): 0.2 ... 0.5 K or 0.08 ... 0.2 % resistance transmitter (Ω): ± 0.1 ... 1.5 Ω or 0.08 ... 0.12 % thermocouple (TC): typ. 0.5 ... 2.0 K or 0.08 % voltage transmitter: ± 20 µV or 0.08 % |
| Output signal | 4 ... 20 mA, 20 ... 4 mA temperature linear, resistance linear, voltage linear |
| Reference operating conditions | calibration temperature 23 °C (296 K) ± 5 K |
| Relative humidity | moisture condensation allowable |
| Response time | 1 s |
| Sensor types | resistance thermometer (RTD): - Pt100, Pt500, Pt1000 acc. to IEC 751 and Ni100, Ni500, Ni1000 acc. to DIN 43760 resistance transmitter (Ω) thermocouple (TC): - B (PtRh30-PtRh6), C (W5Re-W26Re), D (W3Re-W25Re), E (NiCr-CuNi), J (Fe-CuNi), K (NiCr-Ni), L (Fe-CuNi), N (NiCrSi-NiSi), R (PtRh13-Pt), S (PtRh10-Pt), T (Cu-CuNi), U (Cu-CuNi), MoRe5-MoRe41 acc. to IEC 584, part 1 voltage transmitter (mV) |
| Signal on alarm | measuring range undercut: linear drop to 3.8 mA exceeding measuring range: linear rise to 20.5 mA sensor breakage, sensor short circuit: ≤ 3.6 mA oder ≥ 21.0 mA can be set up |
| Supplementary documentation | technical information TI070O operating instructions KA141O safety information SI085O (ZELM 07 ATEX 0352 X) |
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
| Type of protection | II 1G Ex ia IIC T6/T5/T4 |
| Vibration resistance | 4 g/2 ... 150 Hz |