Поиск аналогов электронных компонентов
44003
Pepperl+Fuchs, Inc.Германия

44003

Производится

G11 analog module, 2 analog inputs

Подобрать аналогСпросить AI FAE

Все аналоги

Полный отчёт

Технические параметры

Питание
Auxiliary voltage (output)U AUX | 20 ... 30 V DC PELV
Current loading capacity≤ 140 mA from AS-Interface; overload and short-circuit resistant ≤ 600 mA from external auxiliary voltage U AUX , overload and short-circuit protected
Measuring currentfor Pt100: approx. 1 mA
Rated operating currentI e | ≤ 60 mA (without sensors) / max. 200 mA
Rated operating voltageU e | 26.5 ... 31.6 V from AS-Interface
Supplyfrom AS-Interface (switch position INT, default settings) or auxiliary voltage U EXT (switch position EXT)
Характеристики по постоянному и переменному току
AccuracyVoltage/current: 0.1% of accumulated value Pt100: 0.1% of indicated temperature [°C] + 0.3 °C
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Resolution16 Bit / 1 µA (current input) or 16 bit / 1 mV (voltage input) or 16 Bit / 0.1°C (temperature input)
Условия эксплуатации и корпус
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Height35 mm
Height 35 mm Diameter 85 mmHeight | 35 mm | Diameter | 85 mm
Housing PBT PC Mounting screw Stainless steel 1.4305 / AISI 303Housing | PBT PC | Mounting screw | Stainless steel 1.4305 / AISI 303
MountingMounting plate
Mounting screwStainless steel 1.4305 / AISI 303
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Temperature influenceVoltage/current: 20 ppm/K Pt100: (10 ppm of indicated temperature [°C] + 0.003 °C)/K
Другое
Altitude≤ 2000 m above MSL
AS-InterfaceEN 62026-2:2013
AS-Interface specificationV3.0
Climatic conditionsFor indoor use only
ConnectionAS-Interface/U AUX : cable piercing method, flat cable yellow/flat cable black Inputs: M12 round connector
Degree of protectionEN 60529:2000
Diameter85 mm
Directive 2014/30/EUEN 62026-2:2013
Directive 2014/30/EU EN 62026-2:2013Directive 2014/30/EU | EN 62026-2:2013
Emitted interferenceEN 61000-6-4:2007
Fieldbus standardEN 62026-2:2013
HousingPBT PC
ID1 codeF
ID2 codeD
ID code3
InputEN 61131-2:2007
Input resistancecurrent input: max. 70 Ω voltage input: 100 kΩ
IO code7
IO code 7 ID code 3 ID1 code F ID2 code DIO code | 7 | ID code | 3 | ID1 code | F | ID2 code | D
LED ANALOGstatus of input signal; LED yellow off: not active on: signal within measuring range flashing: signal outside of measuring range
LED AS-i/FAULTStatus display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: peripheral fault
LED AUXext. auxiliary voltage U AUX ; dual LED green/red green: voltage OK red: reverse voltage
LED INT/EXTstatus display input supply; LED green green: input supply from AS-Interface off: input supply from auxiliary voltage
Mass200 g
Node typeStandard node
Number/Type2 analog inputs Current: 0 ... 20 mA/4 ... 20 mA voltage: 0 ... 10 V Pt100: -200 ... 850 °C
Pollution degree3
ProfileS-7.3.D
Protection classIII
Relative humidity85 % , non-condensing
Required gateway specification≥ V2.1
Surge protectionU AUX , U in : Over voltage category III, safe isolated power supplies (PELV)
Tightening torque, cable gland0.4 Nm
Tightening torque, housing screws1.8 Nm
UL File NumberE223772

Изображения