Pulse drive is used in a control motor, for example, so reflected waves resulting from impedance mismatching between the cable, motor, and control section are superimposed on the signal, resulting in surges which become high voltage noise surges.
Все аналоги
Полный отчётТехнические параметры
| Питание | |
|---|---|
| Micro-surge voltage | 1000V or less (between phases) |
| Характеристики по постоянному и переменному току | |
| Carrier frequency | 15kHz or less |
| Output frequency | 0.1Hz~400Hz |
| Условия эксплуатации и корпус | |
| Ambient temperature (°C) | -20°C ~ +40°C |
| Другое | |
| Altitude (m) | 1000m or less |
| Ambient humidity (%RH) | 85%RH or less (No condensation) |
| Applicable inverter | Power source voltage |
| Applicable motor wiring length | 100m or less |
| Environmental compliance | Compliant with the RoHS Directive |
| Insulator resistance (MΩ・km) | 50MΩ or more |
| Inverter capacity | 75kW or less We manufacture units individually for motors exceeding 75kW. |
| Official series page | https://www.okidensen.co.jp/en/prod/cool/ecof.html |
| Outer diameter (termination section / cable section) | Maximum outer diameter at the termination section: approx. 22 mm; Standard cable outer diameter: 9.8 mm. |
| Product name | SSF-L(1)-A(2)-M(3)(*1) |
| Standard weight | 12.5kg |
| Vibration (G) | 0.7G or less |