Все аналоги
Полный отчётТехнические параметры
| Питание | |
|---|---|
| Current | I e | 45 mA |
| Current limit | I max | 45 mA |
| Inrush current | ≤ 200 mA after 100 µs |
| Maximum safe voltage | U m | 250 V (Attention! The rated voltage can be lower.) |
| Maximum safe voltage U m 250 V (Attention! The rated voltage can be lower.) | Maximum safe voltage | U m | 250 V (Attention! The rated voltage can be lower.) |
| Open loop voltage | U s | min. 23.6 V |
| Output/power supply | safe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 V rms |
| Power | P o | 850 mW (angular characteristic curve) |
| Power consumption | max. 3.5 W at 45 mA output current |
| Power supply/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Rated current | I r | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 20 mA (minimum load current DO card) |
| Rated voltage | U r | 18 ... 30 V DC |
| Test current | max. 350 µA , calculated by I LFD = 3.3 V / (10 kΩ + R Load ) |
| Test current max. 350 µA , calculated by I LFD = 3.3 V / (10 kΩ + R Load ) | Test current | max. 350 µA , calculated by I LFD = 3.3 V / (10 kΩ + R Load ) |
| Voltage | U e | ≥ 15 V |
| Характеристики по постоянному и переменному току | |
| Energized/De-energized delay | ≤ 20 ms / ≤ 20 ms |
| Условия эксплуатации и корпус | |
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) , both channels configured in the bus powered mode of operation -40 ... 60 °C (-40 ... 140 °F) , all other configurations extended ambient temperature range up to 70 °C (158 °F) for other configurations, refer to manual for necessary mounting conditions |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Другое | |
| Configuration | via DIP switches |
| Connection | Power Rail or terminals 14+, 15- |
| Connection side | control side |
| Control drawing | 116-0488 |
| Control drawing 116-0488 | Control drawing | 116-0488 |
| Control elements | DIP switch |
| Degree of protection | IP20 |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Directive 2014/30/EU EN 61326-1:2013 (industrial locations) | Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 |
| Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 | Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 |
| Display elements | LEDs |
| Electromagnetic compatibility | NE 21:2017 , EN IEC 61326-1:2021 (industrial locations) , EN IEC 61326-3-2:2018 For further information see system description. |
| EU-type examination certificate | FIDI 21 ATEX 0091 X |
| IECEx certificate | IECEx FIDI 21.0009X |
| IECEx certificate IECEx FIDI 21.0009X IECEx marking Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I | IECEx certificate | IECEx FIDI 21.0009X | IECEx marking | Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I |
| IECEx marking | Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I |
| Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Internal resistance | R i | 167 Ω |
| Internal resistor | R i | approx. 167 Ω |
| Labeling | space for labeling at the front |
| Load | nominal 0.05 ... 20 kΩ , valid range for line fault detection (LFD) |
| Marking | II 3(1)G Ex ec [ia Ga] IIC T4 Gc [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I |
| Mass | approx. 150 g |
| Output | Ex ia Refer to certificate for alternative parameters. |
| Signal level | loop powered 1-signal: 18 ... 30 V DC 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 30 V DC (current limited to 5 mA) 0-signal: 0 ... 5 V DC |
| Signal type | Digital Output |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Test pulse length | max. 2 ms from DO card |
| UL approval | E106378 |
Изображения
Документы