Все аналоги
Полный отчётТехнические параметры
| Питание | |
|---|---|
| Field circuit/control circuit safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Maximum safe voltage | 250 V (Attention! U m is no rated voltage.) |
| Maximum safe voltage 250 V (Attention! U m is no rated voltage.) | Maximum safe voltage | 250 V (Attention! U m is no rated voltage.) |
| Nominal voltage | 24 V DC , in consideration of rated voltage of used isolators |
| Power dissipation | ≤ 500 mW , without modules |
| Supply | Redundancy available. The supply for the isolators is decoupled, monitored and fused. |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered |
| Характеристики по постоянному и переменному току | |
| Ripple | ≤ 10 % |
| Условия эксплуатации и корпус | |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Dimensions | 273 x 155 x 153 mm (10.7 x 6.1 x 6.0 inch) (W x H x D) , depth including module assembly |
| Height | 155 mm |
| Height 155 mm Width 273 mm Depth 153 mm | Height | 155 mm | Width | 273 mm | Depth | 153 mm |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) |
| Другое | |
| Certificate | DEMKO 18 ATEX 2116 X |
| Connection | TB3: terminals 2, 4(+); 1, 3(-) |
| Contact loading | 30 V DC , 1 A |
| Control drawing | 116-0327 |
| Control drawing 116-0327 | Control drawing | 116-0327 |
| Control side | non-explosion hazardous area: 37-pin Sub-D connector |
| Core cross section | screw terminals: 0.25 ... 2.5 mm 2 (24 ... 12 AWG) |
| Degree of protection | IEC 60529:2001 |
| Depth | 153 mm |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Directive 2014/30/EU EN 61326-1:2013 (industrial locations) | Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000 |
| Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000 | Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000 |
| Display elements | LED Supply1 (power supply termination board), green LED LED Supply2 (power supply termination board), green LED LED Fault Status (fault indication), green LED - LED lits: no module fault/no power supply fault |
| Electromagnetic compatibility | NE 21:2017 For further information see system description. |
| EU-type examination certificate | CESI 06 ATEX 022 |
| Fault output | pluggable screw terminals , black |
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Field side | explosion hazardous area: pluggable screw terminals , blue |
| Fusing | 4 A , in each case for 16 modules |
| IECEx certificate | IECEx CES 06.0003 IECEx UL 18.0111 X |
| IECEx certificate IECEx CES 06.0003 IECEx UL 18.0111 X IECEx marking [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I Ex ec nC IIC T4 Gc | IECEx certificate | IECEx CES 06.0003 IECEx UL 18.0111 X | IECEx marking | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I Ex ec nC IIC T4 Gc |
| IECEx marking | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I Ex ec nC IIC T4 Gc |
| Marking | II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I |
| Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I | Marking | II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I |
| Marking II 3G Ex ec nC IIC T4 Gc | Marking | II 3G Ex ec nC IIC T4 Gc |
| Mass | approx. 825 g |
| Material | housing: polycarbonate |
| Output type | volt-free contact |
| Reverse polarity protection | yes |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Switch behaviour | no fault: relay contact closed power supply fault: relay contact open module fault: relay contact open |
| UL approval | E106378 |
| Width | 273 mm |
Изображения
Документы
К этому компоненту пока не привязаны документы.