Поиск аналогов электронных компонентов
61557
Pepperl+Fuchs, Inc.Германия

61557

Производится

Termination Board

Спросить AI FAE

Все аналоги

Полный отчёт

Технические параметры

Питание
Field circuit/control circuit safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 VField circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Maximum safe voltage250 V (Attention! U m is no rated voltage.)
Maximum safe voltage 250 V (Attention! U m is no rated voltage.)Maximum safe voltage | 250 V (Attention! U m is no rated voltage.)
Nominal voltage24 V DC , in consideration of rated voltage of used isolators
Power dissipation≤ 500 mW , without modules
SupplyRedundancy available. The supply for the isolators is decoupled, monitored and fused.
Voltage drop0.9 V , voltage drop across the series diode on the termination board must be considered
Характеристики по постоянному и переменному току
Ripple≤ 10 %
Условия эксплуатации и корпус
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Dimensions432 x 200 x 163 mm (17 x 7.9 x 6.42 inch) (W x H x D) , depth including module assembly
Height200 mm
Height 200 mm Width 432 mm Depth 163 mmHeight | 200 mm | Width | 432 mm | Depth | 163 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Storage temperature-40 ... 70 °C (-40 ... 158 °F)
Другое
ConnectionX20: terminals 3, 5(+); 4, 6(-)
Contact loading30 V DC, 1 A
Control drawing116-0327
Control drawing 116-0327Control drawing | 116-0327
Control sidenon-explosion hazardous area: 2 37-pin Sub-D connector
Core cross sectionscrew terminals: 0.25 ... 1.5 mm 2 (24 ... 12 AWG)
Degree of protectionIEC 60529:2001
Depth163 mm
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)Directive 2014/30/EU | EN 61326-1:2013 (industrial locations)
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 50303:2000
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 50303:2000Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 50303:2000
Display elementsLED PWR1 (termination board power supply), green LED LED PWR2 (termination board power supply), green LED LED FAULT (fault indication), red LED - LED lits: module fault - LED flashes: power supply fault
Electromagnetic compatibilityNE 21:2017 For further information see system description.
EU-type examination certificateCESI 06 ATEX 022
Fault outputpluggable screw terminals , black
Field circuit/control circuitsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Field sideexplosion hazardous area: 4 screw terminals per module , blue
Fusing4 A , in each case for 32 modules
IECEx certificateIECEx CES 06.0003
IECEx certificate IECEx CES 06.0003 IECEx marking [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] IIECEx certificate | IECEx CES 06.0003 | IECEx marking | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I
IECEx marking[Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I
MarkingII (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] IMarking | II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Massapprox. 1430 g
Materialhousing: polycarbonate, 10 % glass fiber reinforced
Output typevolt-free contact
Reverse polarity protectionyes
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Switch behaviourno fault: relay contact closed power supply fault: relay contact open module fault: relay contact open
UL approvalE106378
Width432 mm

Изображения

Документы

К этому компоненту пока не привязаны документы.